TUV certified Type 1+2 AC Surge Protection Device

  • TUV certified Type 1+2 AC Surge Protection Device
  • TUV certified Type 1+2 AC Surge Protection Device
  • TUV certified Type 1+2 AC Surge Protection Device
  • TUV certified Type 1+2 AC Surge Protection Device
  • TUV certified Type 1+2 AC Surge Protection Device
  • TUV certified Type 1+2 AC Surge Protection Device
TUV certified Type 1+2 AC Surge Protection Device
  • Prosurge
  • China
  • 4-5 weeks
  • 30kpcs/month

TUV certified T1+ T2 SPD per IEC/EN 61643-11 standard and Use in TN/TT systems; Lightning current capacity up to 7.5 kA10/350μs(L-N), 12.5kA 10/350μs( (N-PE), Surge current capability up to 50kA 8/20μs;
Unique thermal disconnector design provides quick thermal response and secure disconnection, Low voltage protection level.
High short-circuit current rating up to 25kArms, suitable for application in most AC power system, Degradation failure indication and optional remote signal contact; Pluggable module for easy replacement without the need to remove system wiring.
Wide operating temperature -40ºC ~85ºC, 35mm DIN-rail mounting, Comply with UL1449 5th, IEEE C62.41,CSA C22.2 standards

The DT50/DS50 series are class I & class II (or T1+T2 ) SPD designed for low-voltage power system lightning current & surge protection, used at the boundaries from lightning protection zone 0B -2 and higher.

With built in PROSURGE high energy MOV and GDT, DT50 and DS50 series SPD ensures remarkable lightning current discharge capacity up to 7.5 kA 10/350μs(L-N), 12.5kA (N-PE) and high reliability. The unique design of thermal protection provides quick thermal response and secure disconnection.


Single Pole  L-N

V50/Uc-S

Part No.

V50/75(-S)

V50/150(-S)

V50/180(-S)

V50/275(-S)

V50/320(-S)

V50/350(-S)

V50/385 (-S)

V50/440(-S)

V50/480(-S)

V50/600(-S)

V50/750(-S)

In accordance with

IEC/EN 61643-11:2011; UL1449 5th

Category IEC/EU/VDE

I+ II /1+2/ B+C

Protection mode

L-N or L-PE or N-PE

Nominal Voltage (AC)  Un

60V

120V

120V

230V

230V

277V

277V

400V

400V

480V

600V

Power frequency

50/60Hz

Max. continuous operating voltage(AC) Uc

75V

150V

180V

275V

320V

350V

385V

440V

480V

600V

750V

Nominal discharge current(8/20)  In

20kA

Max. discharge current(8/20)  Imax

50kA

Lightning impulse current (10/350)  Iimp

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

6.0kA

4.5kA

4.5kA

3.5kA

Voltage protection level  Up

0.6kV

0.8kV

1.0kV

1.2kV

1.4kV

1.5kV

1.8kV

2.0kV

2.2kV

2.5kV

2.8kV

Response time  tA

25 ns

Temporary overvoltage TOV  UT

Withstand mode  

90V/5s

174V/5s

228V/5s

335V/5s

335V/5s

403V/5s

403V/5s

580V/5s

580V/5s

700V/5s

870V/5s

Follow current & interrupt rating  Ifi

No

Leakage current   Ipe

<0.1mA

Short-circuit current rating  Isscr

25kArms

Backup fuse(only required if not already provided in mains)

125A gL/gG

Operating temperature range

-40ºC ~ +85ºC

Altitude

-500m ~ +4000m

Cross-section of connection wire (max)

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Enclosure material

Thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

Installation width

1 module, DIN 43880

Thermal disconnector

Internal  Green – normal ; red - failure

Remote alarm contact

Optional

Approvals, Certifications

TUV, CE

Additional data for Remote Alarm Contacts

Remote alarm contact type

Isolated Form C

Switching capability Un/In

AC: 250V/0.5A     DC: 250V/0.1A; 125V/0.2A; 75V/0.5A

Cross-section of remote signaling wire

Max. 1.5mm2(or # 16AWG)



Single Phase - 2 Poles  "2+0"

DS50/Uc-2V-S

Part No.

DS50/75-2V(-S)

DS50/150-2V(-S)

DS50/180-2V(-S)

DS50/275-2V(-S)

DS50/320-2V(-S)

DS50/350-2V(-S)

DS50/385-2V (-S)

DS50/440-2V(-S)

DS50/480-2V(-S)

DS50/600-2V(-S)

DS50/750-2V(-S)

In accordance with

IEC/EN 61643-11:2011; UL1449 5th

Category IEC/EU/VDE

I+ II /1+2/ B+C

Protection mode

L-PE ,N-PE

Nominal Voltage (AC)   Un

60V

120V

120V

230V

230V

277V

277V

400V

400V

480V

600V

Power frequency

50/60Hz

Max. continuous operating voltage(AC) Uc

75V

150V

180V

275V

320V

350V

385V

440V

480V

600V

750V

Nominal discharge current(8/20)   In

20kA

Max. discharge current(8/20)   Imax

50kA

Lightning impulse current (10/350)  Iimp

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

6.0kA

4.5kA

4.5kA

3.5kA

Voltage protection level  Up

0.6kV

0.8kV

1.0kV

1.2kV

1.4kV

1.5kV

1.8kV

2.0kV

2.2kV

2.5kV

2.8kV

Response time  tA

25 ns

Temporary overvoltage TOV  UT

Withstand mode  

90V/5s

174V/5s

228V/5s

335V/5s

335V/5s

403V/5s

403V/5s

580V/5s

580V/5s

700V/5s

870V/5s

Follow current & interrupt rating  Ifi

No

Leakage current  Ipe

<0.1mA

Short-circuit current rating  Isscr

25kArms

Backup fuse(only required if not already provided in mains)

125A gL/gG

Operating temperature range

-40ºC ~ +85ºC

Altitude

-500m ~ +4000m

Cross-section of connection wire (max)

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Enclosure material

Thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

Installation width

2 module, DIN 43880

Thermal disconnector

Internal  Green – normal ; red - failure

Remote alarm contact

Optional

Approvals, Certifications

TUV, CE

Additional data for Remote Alarm Contacts

Remote alarm contact type

Isolated Form C

Switching capability Un/In

AC: 250V/0.5A     DC: 250V/0.1A; 125V/0.2A; 75V/0.5A

Cross-section of remote signaling wire

Max. 1.5mm2(or # 16AWG)



Single Phase - 2 Poles  "1+1"

DS50/Uc-(V+T)-S

Part No.

DS50/150-(V+T) (-S)

DS50/180-(V+T) (-S)

DS50/275-(V+T) (-S)

DS50/320-(V+T) (-S)

DS50/350-(V+T) (-S)

DS50/385-(V+T) (-S)

In accordance with

IEC/EN 61643-11:2011; UL1449 5th

Category IEC/EU/VDE

I+ II /1+2/ B+C

Protection mode

L-PE ,N-PE

Nominal Voltage (AC)  Un

120V

120V

230V

230V

277V

277V

Power frequency

50/60Hz

Max. continuous operating voltage(AC)  Uc

L-N

150V

180V

275V

320V

350V

385V

N-PE

150V

150V

255V

255V

255V

255V

Nominal discharge current(8/20)  In

20kA

Max. discharge current(8/20)  Imax

50kA

Lightning impulse current (10/350) Iimp

L-N

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

N-PE

12.5kA

12.5kA

12.5kA

12.5kA

12.5kA

12.5kA

Voltage protection level  Up

L-N

0.8kV

1.0kV

1.2kV

1.4kV

1.5kV

1.8kV

N-PE

1.5kV

1.5kV

1.5kV

1.5kV

1.5kV

1.5kV

Response time  tA

L-N

25 ns

N-PE

100 ns

Temporary overvoltage TOV  UT

Withstand mode  

L-N

174V/5s

228V/5s

335V/5s

335V/5s

403V/5s

403V/5s

N-PE

1200V/200ms

1200V/200ms

1200V/200ms

1200V/200ms

1200V/200ms

1200V/200ms

Follow current & interrupt rating  Ifi

N-PE

100A

Leakage current   Ipe

<0.1mA

Short-circuit current rating  Isscr

25kArms

Backup fuse(only required if not already provided in mains)

125A gL/gG

Operating temperature range

-40ºC ~ +85ºC

Altitude

-500m ~ +4000m

Cross-section of connection wire (max)

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Enclosure material

Thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

Installation width

2 module, DIN 43880

Thermal disconnector

Internal  Green – normal ; red - failure

Remote alarm contact

Optional

Approvals, Certifications

TUV, CE

Additional data for Remote Alarm Contacts

Remote alarm contact type

Isolated Form C

Switching capability Un/In

AC: 250V/0.5A     DC: 250V/0.1A; 125V/0.2A; 75V/0.5A

Cross-section of remote signaling wire (max)

1.5mm2(or # 16AWG)




Three Phase - 3 Poles  "3+0"

DT50/Uc-3V-S

Part No.

DT50/75-3V(-S)

DT50/150-3V(-S)

DT50/180-3V(-S)

DT50/275-3V(-S)

DT50/320-3V(-S)

DT50/350-3V(-S)

DT50/385-3V (-S)

DT50/440-3V(-S)

DT50/480-3V(-S)

DT50/600-3V(-S)

DT50/750-3V(-S)

In accordance with

IEC/EN 61643-11:2011; UL1449 5th

Category IEC/EU/VDE

I+ II /1+2/ B+C

Protection mode

L-PE ,N-PE

Nominal Voltage (AC)  Un

60V

120V

120V

230V

230V

277V

277V

400V

400V

480V

600V

Power frequency

50/60Hz

Max. continuous operating voltage(AC) Uc

75V

150V

180V

275V

320V

350V

385V

440V

480V

600V

750V

Nominal discharge current(8/20)  In

20kA

Max. discharge current(8/20)  Imax

50kA

Lightning impulse current (10/350)  Iimp

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

6.0kA

4.5kA

4.5kA

3.5kA

Voltage protection level   Up

0.6kV

0.8kV

1.0kV

1.2kV

1.4kV

1.5kV

1.8kV

2.0kV

2.2kV

2.5 V

2.8kV

Response time  tA

25 ns

Temporary overvoltage TOV  UT

Withstand mode  

90V/5s

174V/5s

228V/5s

335V/5s

335V/5s

403V/5s

403V/5s

580V/5s

580V/5s

700V/5s

870V/5s

Follow current & interrupt rating  Ifi

No

Leakage current   Ipe

<0.1mA

Short-circuit current rating    Isscr

25kArms

Backup fuse(only required if not already provided in mains)

125A gL/gG

Operating temperature range

-40ºC ~ +85ºC

Altitude

-500m ~ +4000m

Cross-section of connection wire (max)

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Enclosure material

Thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

Installation width

3 module, DIN 43880

Thermal disconnector

Internal  Green – normal ; red - failure

Remote alarm contact

Optional

Approvals, Certifications

TUV, CE

Additional data for Remote Alarm Contacts

Remote alarm contact type

Isolated Form C

Switching capability Un/In

AC: 250V/0.5A     DC: 250V/0.1A; 125V/0.2A; 75V/0.5A

Cross-section of remote signaling wire

Max. 1.5mm2(or # 16AWG)




Three Phase - 4 Poles  "4+0"

DT50/Uc-4V-S

Part No.

DT50/75-4V(-S)

DT50/150-4V(-S)

DT50/180-4V(-S)

DT50/275-4V(-S)

DT50/320-4V(-S)

DT50/350-4V(-S)

DT50/385-4V (-S)

DT50/440-4V(-S)

DT50/480-4V(-S)

DT50/600-4V(-S)

DT50/750-4V(-S)

In accordance with

IEC/EN 61643-11:2011; UL1449 5th

Category IEC/EU/VDE

I+ II /1+2/ B+C

Protection mode

L-PE ,N-PE

Nominal Voltage (AC)  Un

60V

120V

120V

230V

230V

277V

277V

400V

400V

480V

600V

Power frequency

50/60Hz

Max. continuous operating voltage(AC) Uc

75V

150V

180V

275V

320V

350V

385V

440V

480V

600V

750V

Nominal discharge current(8/20)  In

20kA

Max. discharge current(8/20)  Imax

50kA

Lightning impulse current (10/350)  Iimp

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

6.0kA

4.5kA

4.5kA

3.5kA

Voltage protection level  Up

0.6kV

0.8kV

1.0kV

1.2kV

1.4kV

1.5kV

1.8kV

2.0kV

2.2kV

2.5kV

2.8kV

Response time  tA

25 ns

Temporary overvoltage TOV  UT

Withstand mode  

90V/5s

174V/5s

228V/5s

335V/5s

335V/5s

403V/5s

403V/5s

580V/5s

580V/5s

700V/5s

870V/5s

Follow current & interrupt rating  Ifi

No

Leakage current  Ipe

<0.1mA

Short-circuit current rating  Isscr

25kArms

Backup fuse(only required if not already provided in mains)

125A gL/gG

Operating temperature range

-40ºC ~ +85ºC

Altitude

-500m ~ +4000m

Cross-section of connection wire (max)

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Enclosure material

Thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

Installation width

4 module, DIN 43880

Thermal disconnector

Internal  Green – normal ; red - failure

Remote alarm contact

Optional

Approvals, Certifications

TUV, CE

Additional data for Remote Alarm Contacts

Remote alarm contact type

Isolated Form C

Switching capability Un/In

AC: 250V/0.5A     DC: 250V/0.1A; 125V/0.2A; 75V/0.5A

Cross-section of remote signaling wire

Max. 1.5mm2(or # 16AWG)



Three Phase - 4 Poles  "3+1" 

DT50/Uc-(3V+T)-S

Part No.

DT50/150-(3V+T) (-S)

DT50/180-(3V+T) (-S)

DT50/275-(3V+T) (-S)

DT50/320-(3V+T) (-S)

DT50/350-(3V+T) (-S)

DT50/385-(3V+T) (-S)

In accordance with

IEC/EN 61643-11:2011; UL1449 5th

Category IEC/EU/VDE

I+ II /1+2/ B+C

Protection mode

L-PE ,N-PE

Nominal Voltage (AC)  Un

120V/208V

120V/208V

230V/400V

230V/400V

277V/480V

277V/480V

Power frequency

50/60Hz

Max. continuous operating voltage(AC)  Uc

L-N

150V

180V

275V

320V

350V

385V

N-PE

150V

150V

255V

255V

255V

255V

Nominal discharge current(8/20)  In

20kA

Max. discharge current(8/20)  Imax

50kA

Lightning impulse current (10/350) Iimp

L-N

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

7.5kA

N-PE

12.5kA

12.5kA

12.5kA

12.5kA

12.5kA

12.5kA

Voltage protection level  Up

L-N

0.8kV

1.0kV

1.2kV

1.4kV

1.5kV

1.8kV

N-PE

1.5kV

1.5kV

1.5kV

1.5kV

1.5kV

1.5kV

Response time  tA

L-N

25 ns

N-PE

100 ns

Temporary overvoltage TOV  UT

Withstand mode  

L-N

174V/5s

228V/5s

335V/5s

335V/5s

403V/5s

403V/5s

N-PE

1200V/200ms

1200V/200ms

1200V/200ms

1200V/200ms

1200V/200ms

1200V/200ms

Follow current & interrupt rating  Ifi

N-PE

100A

Leakage current  Ipe

<0.1mA

Short-circuit current rating  Isscr

25kArms

Backup fuse(only required if not already provided in mains)

125A gL/gG

Operating temperature range

-40ºC ~ +85ºC

Altitude

-500m ~ +4000m

Cross-section of connection wire (max)

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Enclosure material

Thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

Installation width

4 module, DIN 43880

Thermal disconnector

Internal  Green – normal ; red - failure

Remote alarm contact

Optional

Approvals, Certifications

TUV, CE

Additional data for Remote Alarm Contacts

Remote alarm contact type

Isolated Form C

Switching capability Un/In

AC: 250V/0.5A     DC: 250V/0.1A; 125V/0.2A; 75V/0.5A

Cross-section of remote signaling wire (max)

1.5mm2(or # 16AWG)


TUV DT50, DS50.. Basic circuit diagram and Dimension.pdf