Panel SPD - 25kA to 50kA per phase - In 10kA

  • Panel SPD - 25kA to 50kA per phase - In 10kA
  • Panel SPD - 25kA to 50kA per phase - In 10kA
Panel SPD - 25kA to 50kA per phase - In 10kA
  • Prosurge
  • China
  • 30 days after receiving payment
  • 5000pcs per month

PROSURGE PSPE series panel SPDs are extra compact UL Type 1 Surge Protective Devices (SPDs) designed to protect single phase and multi-phase electrical distribution systems against the harmful effects of transient surges.

Features:
 UL 1449 5th Type 1 SPDs with SCCR up to 200kArms without external fuse or CB
 Nominal discharge current: 10kA(8/20μs)
 Max surge current: 25~50kA (8/20μs) per phase
 Short circuit current rating SCCR: 200kArms - tested without external CB or fuse
 Full modes protection
 Low voltage protection rating
 Degradation failure indication.
 NEMA 4X enclosure


PROSURGE® PSP E series panel SPDis constructed with Prosurge’s patented PTMOV, which has a thermally protected and arc extinguishing technology as the core of Prosurge’s competency. PSP E has a significant advantage in abnormal over-voltage & high fault current safety and thus ensures industry’s highest level of safety and performance.


PSP E is tested and listed as Type 1 SPD in ANSI / UL 1449 5th, CSA C22.2. It is constructed in a NEMA 4X plastic enclosure, with a LED light to demonstrate the protection status of the SPD.


Typical Applications:

  • Outdoor/Indoor and commercial LED lighting

  • Telecommunication equipment

  • Medical electronics

  • Security & Alarm equipment

  • Manufacturing Facilities

  • Other Critical Electronic Equipment


General Specification:

PSP Category

PSPE

Certification

ANSI / UL1449 5th, CSA C22.2, Type 1 

Connection Type

Parallel Connected

Surge Capacity

25-50kA per Phase

Nominal discharge current In

10kA

SCCR

200kArms

Power Status Indication

Normal= LED ON

Working Status Indication

Fail= LED OFF

Power Connecting  

12AWG, 762mm (30”) length

Working environments

Temperature –40+80, Humidity relative 5~95% (25), Altitude≤3km

Dimensions (W x D x H)

90 x 58 x 41 mm

Enclosure

Plastic enclosure, NEMA 4X

Threaded NPT

1/2"NPT

Net Weight

0.18 kg


Voltage code for power distribution system:

  • 120SP, 240SP= 120/240V;240/480V------Split-phase three-wire + ground (Figure1)

  • 120S,127S,240S,277S,347S =120V,127V, 240V,277V, 347V------Single-phase two-wire + ground (Figure5)

  • 120Y, 127Y, 240Y, 277Y, 347Y = 208Y/120V,220Y/127V, 415Y/240V,480Y/277V, 600Y/347V------Three-phase wye (star) four-wire + ground (Figure2)

  • 240D, 480D, 600D = 240V,480V,600V------Three-phase delta three-wire + ground (Figure4)


SPD for street light