Panel SPD - 400kA to 600kA per phase
- Prosurge
- China
- 30 days after receiving payment
- 3000pcs per month
PROSURGE HPSP series panel SPDs are defined as high performance UL listed Type 1 and Type 2 Surge Protective Devices (SPDs) that protect most commercial and industrial environments against the harmful effects of transient surges.
Features:
UL 1449 5th, CSA C22.2 listed Type 1 SPDs
Nominal discharge current: 20kA (8/20us)
Surge capacity (8/20 us ): 400~600 kA per phase
Lightning current capacity (10/350 us): 40~60kA per phase, EN/IEC 61643-1/11 class I test
Short Circuit current rating (SCCR): 200 kArms - tested without external CB or fuse
UL1283 listed Sine Wave Tracking (EMI/RFI filter) filtering up to -45dB from 10kHz to 100MHz
Full modes protection
Large surge energy capability with compact size
Low voltage protection rating
Degradation failure indication, audible alarm, beep while SPD fail
With surge event counter
With Remote Alarm
NEMA 4X plastic enclosure
PROSURGE® HPSP series panel SPD is constructed with Prosurge’s patented PTMOVs, which has a thermally protected and arc extinguishing technology as the core of Prosurge's competency. PSP C has a significant advantage in abnormal over-voltage & high fault current safety and thus ensures industry’s highest level of safety and performance. The parallel redundancy modules design makes the SPDs extremely robust and reliable, and thus may handle great impulse current up to 600kA (8/20 μs) and multiple impulse current at its highest rated level.
The Prosurge HPSP series are tested and listed as UL1449 5th Type 1 and Type 2 SPD (UL1283 listed sine wave tracking function). Their front panels integrate functionality of SPD working status monitor and self-diagnosis to enhance the performance and usability. They feature with indicator and colored LEDs to demonstrate the power & protection status of each protected power phase. They are constructed with NEMA 4/4X enclosures to ensure that dirt, dust and water are resisted for either indoor or outdoor usage.
Typical Applications in high exposure locations
Commercial
Industrial
Communications
Renewable energy
Critical power (hospitals, data centers, etc)
General Specification:
PSP category | HPSP | |
Certification | ANSI/UL1449 5th edition, CSA C22.2, Type1 SPD ANSI/UL1449 5th edition, CSA C22.2,UL1283, Type2 SPD | |
Connection Type | Parallel Connected | |
Capacity | Surge current | 400-600kA (8/20μs) per Phase |
Lightning current | 40~60kA (10/350μs) per Phase | |
Nominal discharge current In | 20kA | |
SCCR | 200kArms | |
UL1283 EMI/RFI filter | Sine wave tracking, up to -45dB from 10kHz to 100MHz (Type2 only) | |
Lightning counter Current | ≥ 200A (with Reset button ) | |
Failure pre-test | Press 2S (test button) | |
Power Status Indication | Normal=Blue LED ON | |
Working Status Indication | Normal= Blue LED ON; Fail= Blue LED turn to Red Buzzer inside, beep while SPD fail | |
Power Connecting | 10AWG, 762mm (30”) length, (L1=black; L2=red; L3=blue; N=white; PE=green ) | |
Signal cable | 16AWG, 762mm (30”) length,(C=red; NC=blue; NO=brown) | |
Working environments | Temperature –40℃~+75℃, Humidity relative 5~95% (25℃) , Altitude≤3km | |
Dimensions (W x D x H) | 200 x 150 x 100 mm | |
Threaded NPT | 3/4"NPT | |
Enclosure | Plastic enclosure, NEMA 4X | |
Net Weight | 1.8 kg |
Configure & Ordering Information:
PSP Model series | 277Y Voltage and system configuration | C Protection mode | 42 Surge capacity | / T1 SPD Category | CTA Additional function |
HPSP | 120SP: 120/240V split 240SP:240/480V split 120Y:120/1208V WYE 277Y: 277/480V WYE 120H: 120/240V high leg delta 240D: 240V delta 120S:120V 1ph, 2W+G … | C: Delete N-G protection mode
| 42:400kA per phase 52:500kA per phase 62:600kA per phase | T1: UL type 1 SPD T2F: UL type 2 SPD with sine wave tracking UL 1283 listed
| C: surge event counter |