10A Surge Filter
- Prosurge
- China
- 30 days after receiving payment
- 400Kpcs per month
Prosurge surge filter DSF10 is used to protect single phase electrical distribution systems, especially to protect sensitive electronics against the harmful effects of transient surges.
Features:
Multi-stage protection circuit with LC Filter design to protect sensitive electronics.
Provides extensive high frequency & RF filtering
Application for 120~127V, 220~277V (L-N) TT/TN, or any 1-phase system with a grounded neutral
Rated Load current 10A
Built-in backup fuse for over- current protection
All mode protection
DIN-Rail mounting
LED failure indication
Comply with UL1449 4th, IEEE C62.41, CSA C22.2,IEC/EN 61643-11
Technical Data:
Model | DSF10/175-10A/3P/C | DS10/320-10A/3P/C | ||
According to | IEC61643-11; UL1449-4th; IEC610006; ANSI/IEEE C62.41; AS1768-1991;AS3100 | |||
Category IEC/EN/UL | Class III/ Type 3 / Type | |||
Protection Mode | All mode protection | |||
Protection technology | MOV tech, Thermal protection LC filter, Built-in backup fuse | |||
Power system | Un | 120-127V single phase | 220-277V single phase | |
Max. continuous operating voltage (AC/DC) | Uc | 175/230 | 320/420 | |
Rated load Current | Il | 10A | ||
Nominal discharge current(8/20) | In | 5kA | ||
Max. discharge current(8/20) | Imax | 10kA | ||
Voltage impulse(1.2/50us) | Uoc | 10kV | ||
Total surge capacity per Line (8/20us) | Itotal | 40kA | ||
Voltage protection level | L-N @6kV/3kA | VPR | <0.7kV | <1.0kV |
L-N @In | Up | <0.8kV | <1.2kV | |
Residual Current | I PE | <1mA | ||
Voltage drop: | < 2V at rated load current | |||
Temporary overvoltage TOV —Withstand mode | Utov | 195V/5s | 370V/5s | |
Response time | Ta | <5ns | ||
Filter attenuation | dB | >40dB @ 1MHz | ||
Recommended external over current protection in series | 10A Fuse or CB | |||
Protect Status Indication | LED Alarm, Green - Normal, LED off - fail | |||
Connecting cable | multi-strand 2.5mm2 | |||
Environment | Temperature Range:- 10ºC ~ +60ºC Humidity:≤95% Altitude:≤2000m | |||
Mounting | 35mm DIN-rail in accordance with EN 50022/DIN46277-3 | |||
Location Category | Indoor | |||
Degree of protection | IP20 | |||
Dimension | 80(L)×25(W)×85(H) approx | |||
Weight | - approx | |||
Approvals, Certification | , | CE |