25A Surge Filter

  • 25A Surge Filter
  • 25A Surge Filter
25A Surge Filter
  • Prosurge
  • China
  • 30 days after receiving payment
  • 400Kpcs per month

Prosurge surge filter DSF25 is used to protect single phase electrical distribution systems, especially to protect sensitive electronics against the harmful effects of transient surges.

Features:
 Multi-stage protection circuit with LC Filter design to protect sensitive electronics.
 Provides extensive high frequency & RF filtering
 Application for 120~127V, 220~277V (L-N) TT/TN, or any 1-phase system with a grounded neutral
 Surge capacity 25kA 8/20us
 Rated Load current 25A, 16A is available
 Built in backup fuse for fault current protection
 DIN-Rail mounting
 LED failure indication & remote alarm function available
 Comply with UL1449 4th,IEEE C62.41, CSA C22.2,IEC/EN 61643-11




Technical Data:

Model


DSF25/175-25A/3P/C-S

DSF25/320-25A/3P/C-S

According to


IEC61643-11; UL1449-4th; IEC610006; ANSI/IEEE C62.41; AS1768-1991;AS3100

Category IEC/EN/UL


Class III/ Type 3/Type 3

Protection Mode


All mode protecton

Protection technology


MOV tech, Thermal protection

LC filter, Built-in backup fuse

Power system

Un

120-127V single phase

220-277V single phase

Max. continuous operating voltage (AC/DC)

Uc

175/230

320/420

Rated load Current

Il

25A

Nominal discharge current(8/20)

In

L-N 10kA, N-PE 3kA, L-PE 3kA

Max. discharge current(8/20)

Imax

L-N 25kA, N-PE 6kA, L-PE 6kA

Voltage impulse1.2/50us)  

Uoc

10kV

Total surge capacity per Line

Itotal

31 kA (8/20us)

Voltage protection level

L-N @6kV/3kA

VPR

<0.7kV

<1.0kV

L-N @In

Up

<0.8kV

<1.2kV

Residual Current  

I PE

<1mA

Voltage drop:


< 2V at rated load current

Temporary overvoltage TOV

—Withstand mode

Utov

195V/5s

370V/5s

Response time

Ta

<5ns

Filter attenuation

dB

>45dB @ 1MHz

Recommended external over current protection in series


25A Fuse or CB

Protect Status Indication


2 part display, Power OK, Protection fault

Remote alarm


Dry contact alarm relay – 125Vac 1A; 30Vdc, 2A

Connecting cable


Power: single-strand 6mm2; multi-strand 4mm2

Remote:1.5 mm2(or 16AWG)

Environment


Temperature Range- 10ºC ~ +60ºC

Humidity≤95%

Altitude≤2000m

Mounting


35mm DIN-rail in accordance with EN 50022/DIN46277-3

Location Category


Indoor

Degree of protection


IP20

Dimension


90mm (L) x 70mm (W)  x 69mm (H)  approx

Weight


-  approx

Approvals, Certification

,

CE

Get the latest price? We'll respond as soon as possible(within 12 hours)

Privacy policy