16A Surge Filter
- Prosurge
- China
- 30 days after receiving payment
- 400Kpcs per month
Prosurge surge filter BSF40 is used to protect single phase electrical distribution systems, especially to protect sensitive electronics against the harmful effects of transient surges.
Features:
Multi-stage protection circuit with LC Filter design to protect sensitive electronics.
Provides extensive high frequency & RF filtering
Application for 220~277V (L-N) TT/TN, or any single phase system with a grounded neutral
Protection capability 40 kA 8/20us
Load current rating 16A, 10A is available
Built in backup fuse for fault current protection
IEC socket for easy wiring
LED failure indication
All mode protection
Comply with UL1449 4th,IEEE C62.41, CSA C22.2,IEC/EN 61643-11
It’s found that electronic equipment is sensitive to both the absolute magnitude of the impulse voltage and its rise rate. The radical changes in dv/dt and di/dt, rather than the peak voltage, is the major source of electronic circuit damages.
Prosurge surge filter is designed as a 3-stage protection system which consists of primary protection & secondary protection and with a well-designed LC filter in series. The LC filter is used to slow down the inherently fast rise rate of voltage and current. The primary protection module is used to divert the strong lightning/surge current, while the secondary protection module & LC filter will limit the let-through voltage to a very low level.
The surge filter should be installed in series with the supply powering the equipment.
Technical Data:
Model | BSF40-1/320-10A-3P | BSF40-1/320-16A-3P | ||
According to | IEC61643-11; UL1449-4th; IEC610006; ANSI/IEEE C62.41; AS1768-1991;AS3100 | |||
Category IEC/EN/UL | Class II+III/ Type 2+3 / Type 2 | |||
Protection Mode | All mode protecton | |||
Protection technology | MOV tech, Thermal protection LC filter, Built-in backup fuse | |||
Power system | Un | 220-277V single phase | 220-277V single phase | |
Max. continuous operating voltage (AC/DC) | Uc | 320/420 | 320/420 | |
Rated load Current | Il | 10A | 16A | |
Nominal discharge current(8/20) | In | L-N 20kA, N-E 5kA, L-E 5kA | ||
Max. discharge current(8/20) | Imax | L-N 40kA, N-E 10kA, L-E 10kA | ||
Voltage impulse(1.2/50us) | Uoc | 20kV | ||
Total surge capacity per Line | Itotal | 100kA (8/20us) | ||
Voltage protection level | L-N @6kV/3kA | VPR | <1.0kV | |
L/N-PE@6kV/3kA | VPR | <1.2kV | ||
L-N @In | Up | <1.2kV | ||
L/N-PE@In | Ip | <1.4kV | ||
Residual Current | I PE | <1mA | ||
Voltage drop: | < 2V at rated load current | |||
Temporary overvoltage TOV —Withstand mode | Utov | 400V/5s | ||
Response time | Ta | <5ns | ||
Filter attenuation | dB | >40dB @ 1MHz | ||
Recommended external over current protection in series | 10A Fuse or CB | 16A Fuse or CB | ||
Protect Status Indication | 2 part display, Power OK, Protection fault | |||
Connecting cable | IEC320 10A input x 1, IEC320 10A output x 1. | IEC320 16A input x 1, IEC320 16A output x 1. | ||
Environment | Temperature Range:- 10ºC ~ +60ºC Humidity:≤95% Altitude:≤2000m | |||
Mounting | Portable | |||
Location Category | Indoor | |||
Degree of protection | IP20 | |||
Dimension | 152mm (L) x 133mm (W) x 48mm (H) approx | |||
Weight | 0.8kg approx | |||
Approvals, Certification | CE |