40 - 45A Surge Filter
- Prosurge
- China
- 30 days after receiving payment
- 400Kpcs per month
Prosurge surge filter BSF50 is used to protect single phase electrical distribution systems, especially to protect sensitive electronics against the harmful effects of transient surges.
Features:
Multi-stage protection circuit with LC Filter design to protect sensitive electronics.
Provides extensive high frequency & RF filtering
Application for 120~127V, 220~277V (L-N) TT/TN, or any single phase system with a grounded neutral
Protection capability 50 kA 8/20us
Load current rating 45A, 20~32A is available
All mode protection
LED failure indication & remote alarm function available
Comply with UL1449 4th,IEEE C62.41, CSA C22.2,IEC/EN 61643-11
It’s found that electronic equipment is sensitive to both the absolute magnitude of the impulse voltage and its rise rate. The radical changes in dv/dt and di/dt, rather than the peak voltage, is the major source of electronic circuit damages.
Prosurge surge filter is designed as a 3-stage protection system which consists of primary protection & secondary protection and with a well-designed LC filter in series. The LC filter is used to slow down the inherently fast rise rate of voltage and current. The primary protection module is used to divert the strong lightning/surge current, while the secondary protection module & LC filter will limit the let-through voltage to a very low level.
The surge filter should be installed in series with the supply powering the equipment.
Techinical Data:
Model | BSF50-1/180-45A-3P | BSF50-1/320-45A-3P | BSF50-1/420-45A-3P | BSF50-1/550-45A-3P | ||
According to | IEC61643-11; UL1449-4th; IEC610006; ANSI/IEEE C62.41; AS1768-1991;AS3100 | |||||
Category IEC/EN/UL | Class II+III/ Type 2+3 / Type 2 | |||||
Protection Mode | All mode protecton | |||||
Protection technology | MOV tech,Thermal protection LC filter, Built-in backup fuse | |||||
Power system | Un | 120~127V single phase | 220-277V single phase | 347V single phase | 480V single phase | |
Max. continuous operating voltage (AC/DC) | Uc | 180/230 | 320/420 | 420/560 | 550/745 | |
Rated load Current | Il | 45A | ||||
Nominal discharge current(8/20) | In | L-N 20kA, N-E 10kA, L-E 10kA | ||||
Max. discharge current(8/20) | Imax | L-N 50kA, N-E 25kA, L-E 25kA | ||||
Voltage impulse(1.2/50us) | Uoc | 20kV | ||||
Total surge capacity per Line | Itotal | 150kA (8/20us) | ||||
Voltage protection level | L-N @6kV/3kA | VPR | <0.6kV | <1.0kV | <1.4kV | <2.0kV |
L/N-PE@6kV/3kA | VPR | <0.7kV | <1.2kV | <1.6kV | <2.2kV | |
L-N @In | Up | <0.8kV | <1.2kV | <1.6kV | <2.3kV | |
L/N-PE@In | Ip | <0.9kV | <1.4kV | <1.8kV | <2.5kV | |
Residual Current | I PE | <1mA | ||||
Voltage drop: | < 2V at rated load current | |||||
Temporary overvoltage TOV —Withstand mode | Utov | 240V/5s | 400V/5s | 600V/5s | 690V/5s | |
Response time | Ta | <5ns | ||||
Filter attenuation | dB | >60dB @ 1MHz/ >15dB @ 100kHz >0.5dB @ 1kHz | ||||
Recommended external over current protection in series | 45A Fuse or CB | |||||
Protect Status Indication | 2 part display, Power OK, Protection fault | |||||
Remote alarm | Dry contact alarm relay – 250Vac/32Vdc, 5A | |||||
Connecting cable | Power 8-10AWG , Alarm 14 -22AWG, | |||||
Environment | Temperature Range:- 10ºC ~ +60ºC Humidity:≤95% Altitude:≤2000m | |||||
Mounting | Wall mounting | |||||
Location Category | Indoor | |||||
Degree of protection | IP20 | |||||
Dimension | 220mm (L) x 143mm (W) x48 mm (H) approx | |||||
Weight | 1.2kg approx | |||||
Approvals, Certification | CE |